Insulation Tester PCE-IT 150

Insulation Tester up to 15 kV test voltage / Li-Ion battery / Date-time display / Test timer / Adjustable test voltage / External voltage alarm / Automatic switch-off

The insulation tester is designed for insulation measurements with a test voltage of up to 15 kV. The measuring range from 0 ... 30 TΩ and other measuring functions make the tester versatile. With 4 quick selection buttons for common test voltages and the option of setting the voltage in 500 V steps. Pre-configured diagnostic tests, including (PI), dielectric absorption ratio (DAR) and a memory function for 200 measurements. These can be transferred to the software via the interface, which also enables the insulation measuring device to be operated. The insulation tester can also be used to measure AC and DC voltages up to 600 V. The insulation tester is supplied in a robust case that offers IP66 protection even when the lid is closed.

In the course of its normal service life, electrical insulation is exposed to various stresses that lead to its deterioration. This is caused by thermal, mechanical and chemical influences as well as moisture. Although the insulation is designed to withstand these stresses over many years, abnormal stresses can intensify the natural ageing process and drastically shorten the service life. It is therefore advisable to regularly check whether an accelerated ageing process is taking place and, if necessary, to determine whether the effects are reversible.

Highlights

- 15 kV insulation tester
- Insulation resistance up to 30 TΩ
- Polarisation index PI
- Dielectric absorption ratio DAR
- 4 buttons for test voltage
- Memory for 200 measured values
- incl. software

Specification

Direct voltage DC  
Measuring range   30 V ... 600 V
Resolution   1 V
Accuracy   ±(2.0% v.Mw. +3 digits)
   
AC voltage AC  
Measuring range   30 V ... 600 V
Resolution   1 V
Accuracy   ±(2.0% v.Mw. +3 digits)
   
Insulation resistance  
Measuring range   0 GΩ ... 1 GΩ
Resolution   0.001 GΩ
Accuracy   ±(5% v.Mw.+5 digits)
   
Insulation resistance  
Measuring range   1 GΩ ... 10 GΩ
Resolution   0.01 GΩ
Accuracy   ±(5% v.Mw.+5 digits)
   
Insulation resistance  
Measuring range   10 GΩ ... 100 GΩ
Resolution   0.1 GΩ
Accuracy   ±(5% v.Mw.+5 digits)
   
Insulation resistance  
Measuring range   100 GΩ ... 1 TΩ
Resolution   1 GΩ
Accuracy   ±(5% v.Mw.+5 digits)
   
Insulation resistance  
Measuring range   1 TΩ ... 10 TΩ
Resolution   10 GΩ
Accuracy   ±20%
   
Insulation resistance  
Measuring range   10 TΩ ... 30 TΩ
Resolution   100 GΩ
Accuracy   ±20%
   
General technical data  
Measurement functions   HOLD, PI, DAR
Display type   LCD
Memory medium   Internal memory
Memory capacity   200 measurements
Interface   RS232
Automatic switch-off   5 min
Automatic switch-off can be deactivated   no
Test voltage   500 V ... 15 kV
Safety standard   CAT IV 600 V
Menu language   English
Protection class (device)   IP66
Protection class (additional information)   Only with closed lid
Power supply   100 ... 240 V | 50/60 Hz
Plug type   Euro plug device
Weight   6362 g
Dimensions (L x W x H)   325 x 430 x 132 mm
Operating conditions   0 ... 40 °C , 0 ... 80 % r.H
Storage conditions   0 ... 40 °C , 0 ... 80 % r.H
Capacity   5200 mAh
Ask about this product