Insulation Tester / Insulation Meter PCE-IT 110

Insulation Tester / Insulation Meter / Test voltage up to 1000V / LCD color display / Time display / Data memory / Automatic switch-off

The Insulation Tester / Insulation Meter combines the functions of a fully-fledged digital multimeter with a powerful Insulation Tester / Insulation Meter and is ideal for professional applications in industry, trade and energy supply. In addition to measuring voltage, current and resistance, the device also offers frequency and capacitance measurement as well as temperature measurement via the supplied type K thermocouple. The automatic range selection and the 3.5 inch LCD color display enable simple and precise operation. The Insulation Tester / Insulation Meter allows insulation tests with selectable test voltages from 125 V to 1000 V and measures insulation resistances of up to 6000 MΩ. It also supports the measurement of the polarization index (PI) and the absorption ratio (DAR), which enables a well-founded assessment of the insulation quality of cables, motors, control cabinets and electrical systems.

Thanks to the integrated data memory, measurement results can be called up directly on the device for later analysis. The recorded data can be transferred wirelessly to a smartphone or tablet via Bluetooth - particularly practical for documentation and test reports. Other features such as automatic discharge after the measurement, MIN/MAX/PEAK value recording, hold function and a lock button for hands-free operation round off the device. The Insulation Tester / Insulation Meter fulfils the highest safety requirements in accordance with CAT IV 600V / CAT III 1000V and can therefore also be used safely for work in energy distribution and on building technology.

Typical areas of application for this Insulation Tester / Insulation Meter include electrical installation, switch cabinet construction, maintenance of machines and systems, photovoltaic systems, the service sector and technical training centers. With its combination of versatility, precision and modern connectivity, this Insulation Tester / Insulation Meter is a good tool for any professional.

Highlights

- Insulation test voltages 125V, 250V, 500V, 1000V
- Measuring functions: HOLD, MIN, MAX, PEAK
- PI (polarization index), DAR (absorption ratio)
- High voltage and overload indicator
- Diode test
- Automatic discharge
- Automatic switch-off
- Locking button
- Data memory with logger
- Bluetooth for app connection
- Connections for Rogowski coil

Specification

Direct voltage DC  
Measurement range up to   0 ... 600 mV
Resolution   0,1 mV
Accuracy   ±(0.9% +5 digits)
Overload   1000 V
   
Direct voltage DC  
Measurement range up to   600 mV ... 6 V
Resolution   0,001 V
Accuracy   ±(0.9% +5 digits)
   
Direct voltage DC  
Measurement range up to   6 ... 60 V
Resolution   0,01 V
Accuracy   ±(0.9% +5 digits)
   
Direct voltage DC  
Measurement range up to   60 ... 600 V
Resolution   0,1 V
Accuracy   ±(1% +5 digits)
   
Direct voltage DC  
Measurement range up to   600 ... 1000 V
Resolution   1 V
Accuracy   ±(1% +5 digits)
   
Direct current DC  
Measurement range up to   0 ... 200 µA
Resolution   0,1 µA
Accuracy   ±(0.9% +8 digits)
   
Direct current DC  
Measurement range up to   200 µA ... 600 mA
Resolution   0,1 mA
Accuracy   ±(1.2% +3 Digits)
   
Direct current DC  
Measurement range up to   600 mA ... 10 A
Resolution   0,01 A
Accuracy   ±(1.5 % +5 digits)
   
Capacity  
Measurement range up to   0 ... 60 nF
Resolution   0,01 nF
Accuracy   ±(5% +35 digits)
   
Capacity  
Measurement range up to   60 ... 600 nF
Resolution   0,1 nF
Accuracy   ±(2.5 % +8 digits)
   
Capacity  
Measurement range up to   600 nF ... 6 µF
Resolution   0,001 µF
Accuracy   ±(3% +5 digits)
   
Capacity  
Measurement range up to   6 ... 60 µF
Resolution   0,01 µF
Accuracy   ±(3% +5 digits)
   
Capacity  
Measurement range up to   60 ... 600 µF
Resolution   0,1 µF
Accuracy   ±(3% +5 digits)
   
Capacity  
Measurement range up to   600 ... 6000 µF
Resolution   1 µF
Accuracy   ±(2.5% +20 Digits)
   
Temperature K-type  
Measurement range up to   -20 ... +600 °C
Resolution   0,1 °C
Accuracy   ±(3 % of Rd +5 °C)
   
Temperature K-type  
Measurement range up to   600 ... 1000 °C
Resolution   1 °C
Accuracy   ±(3 % of Rd +5 °C)
   
Temperature K-type  
Measurement range up to   -4 ... +600 °F
Resolution   0,1 °F
Accuracy   ±(3% v.Mw. +9°C)
   
Temperature K-type  
Measurement range up to   600 ... 1832 °F
Resolution   1 °F
Accuracy   ±(3% v.Mw. +9°C)
   
AC voltage  
Measurement range up to   0 ... 6 V
Resolution   0,001 V
Accuracy   ±(1% +5 Digits) @50 ... 60 Hz / ±(3% +5 Digits) @61 ... 1000 Hz
Overload   1000 V
Frequency range   50 ... 1000 Hz
   
AC voltage  
Measurement range up to   6 ... 60 V
Resolution   0,01 V
Accuracy   ±(1% +5 Digits) @50 ... 60 Hz / ±(3% +5 Digits) @61 ... 1000 Hz
Frequency range   50 ... 1000 Hz
   
AC voltage  
Measurement range up to   60 ... 600 V
Resolution   0,1 V
Accuracy   ±(1% +5 Digits) @50 ... 60 Hz / ±(3% +5 Digits) @61 ... 1000 Hz
Frequency range   50 ... 1000 Hz
   
AC voltage  
Measurement range up to   600 ... 1000 V
Resolution   1 V
Accuracy   ±(1.2% +5 Digits) @50 ... 60 Hz / ±(3% +5 Digits) @61 ... 1000 Hz
Frequency range   50 ... 1000 Hz
   
Alternating current AC  
Measurement range up to   0 ... 200 µA
Resolution   0,1 µA
Accuracy   ±(1.2% +8 digits)
Frequency range   50 ... 1000 Hz
   
Alternating current AC  
Measurement range up to   200 µA ... 600 mA
Resolution   0,1 mA
Accuracy   ±(1.2 % +5 digits)
Frequency range   50 ... 1000 Hz
   
Alternating current AC  
Measurement range up to   600 mA ... 10 A
Resolution   0,01 A
Accuracy   ±(1.5 % +5 digits)
Frequency range   50 ... 1000 Hz
   
Insulation resistance  
Test voltage DC   125V
Measurement range up to   0,125 ... 6 M Ω
Resolution   0,001 M Ω
Accuracy   ±(2 % +10 digits)
   
Insulation resistance  
Test voltage DC   250V
Measurement range up to   0,25 ... 6 M Ω
Resolution   0,001 M Ω
Accuracy   ±(2% +15 Digits)
   
Insulation resistance  
Test voltage DC   500V
Measurement range up to   0,5 ... 6 M Ω
Resolution   0,001 M Ω
Accuracy   ±(2 % +10 digits)
   
Insulation resistance  
Test voltage DC   1000V
Measurement range up to   1 ... 6 M Ω
Resolution   0,001 M Ω
Accuracy   ±(3% +10 Digits)
   
Insulation resistance  
Test voltage DC   125V, 250V, 500V, 1000V
Measurement range up to   6 ... 60 M Ω
Resolution   0,01 M Ω
Accuracy   ±(2 % +10 digits)
   
Insulation resistance  
Test voltage DC   125V, 250V, 500V, 1000V
Measurement range up to   60 ... 600 M Ω
Resolution   0,1 M Ω
Accuracy   ±(4% +5 digits)
   
Insulation resistance  
Test voltage DC   125V, 250V, 500V, 1000V
Measurement range up to   600 ... 6000 M Ω
Resolution   1 M Ω
Accuracy   ±(5% +10 Digits)
   
Resistance  
Measurement range up to   0 ... 600 Ω
Resolution   0,1 Ω
Accuracy   ±(1.2% +10 digits)
   
Resistance  
Measurement range up to   600 Ω ... 6 kΩ
Resolution   0,001 kΩ
Accuracy   ±(1.5 % +5 digits)
   
Resistance  
Measurement range up to   6 ... 60 kΩ
Resolution   0,01 Ω
Accuracy   ±(1.5 % +5 digits)
   
Resistance  
Measurement range up to   60 ... 600 kΩ
Resolution   0,1 kΩ
Accuracy   ±(1.5 % +5 digits)
   
Resistance  
Measurement range up to   600 kΩ ... 6 M Ω
Resolution   0,001 M Ω
Accuracy   ±(1.5 % +5 digits)
   
Resistance  
Measurement range up to   6 ... 60 M Ω
Resolution   0,01 M Ω
Accuracy   ±(2.5% +10 digits)
   
Frequency  
Measurement range up to   40 ... 10000 Hz
Resolution   0,01 Hz
Accuracy   ±(1% +5 digits)
   
General technical data  
Measuring functions   MIN, MAX, HOLD, PI, DAR
Display type   LC colour display
Display size   3,5 Inch
Display refresh rate   3 x per second
Measuring rate   3 Hz
Storage medium   Internal memory
Storage capacity   1800 Values
Storage interval from   1 s
Storage interval to   60 min.
Interface   Bluetooth
Automatic power-off from...to   15 ... 60 min.
Automatic power-off can be deactivated   Yes
Safety standard   CAT III 1000V, CAT IV 600V
Diode test   Test current: <1.5 mA
Max. Voltage in open circuit: 3.2V DC
Menu language   English, English (GB)
Protection class (device)   IP65
(Rechargeable) battery   6 x 1,5 V AA battery , Alkali-manganese
Capacity   2500 mAh
Operating conditions   5 ... 40 °C , 0 ... 80 % RH
Storage conditions   -20 ... 60 °C , 0 ... 80 % RH
Dimensions ( L x W x H )   215 x 100 x 65 mm
Weight   569 g
Ask about this product