Insulation Tester / Insulation Meter PCE-MO 1500

Insulation Tester / Insulation Meter with memory for measured values / measuring functions: PI/DAR/HOLD / automatic power-off / battery-operated / 3.7 inch LC display with backlight

The Insulation Tester / Insulation Meter was developed to simplify on-site troubleshooting in both industrial systems and solar systems. With selectable test voltages from 250 ... 2500 V and resistance measurement up to 200 GΩ, this device allows multiple operations to be carried out with just one tool. The intuitive user interface, short-circuit current of up to 1.8 mA and CAT IV 600 V safety make these portable high-voltage Insulation Tester / Insulation Meters ideal for quick and stable resistance measurements anywhere.

The test voltage can be variably selected from 250 V, 500 V, 1000 V, 2000 V and 2500 V. It can also measure AC and DC voltages from 10 ... 600 V. The Insulation Tester / Insulation Meter has a memory for 100 data records which can be called up via the LC display. In addition to the data hold function, the Insulation Tester / Insulation Meter offers the option of measuring the polarisation index (PI) and the dielectric absorption ratio (DAR). These functions are particularly useful for condition monitoring and maintenance of electrical insulation, as they help to detect potential problems at an early stage and extend the service life of the equipment. A high-voltage indicator ensures safety during operation and a low-battery indicator indicates in good time that the battery needs to be replaced.

The device is particularly suitable for measuring insulation resistance on various electrical devices and insulating materials such as motors, cables, switches and other electrical components, making it ideal for maintenance, repair and testing work. With its modern design and stable performance, the device is impressive in every respect. The Insulation Tester / Insulation Meter is supplied in a practical zip bag for easy storage and transport.

Highlights

- direct voltage DC
- alternating voltage AC
- selectable test voltages
- measuring functions: PI/DAR/HOLD
- internal memory
- display of measuring time
- automatic discharge
- automatic power-off
- high-voltage display
- safety: EN 61010-1; CAT III 1000V; CAT IV 600 V

Specification

Direct voltage DC  
Measurement range up to   10 ... 600 V
Resolution   1 V
Accuracy   ±(0.8 % of Rd +5 digits)
   
AC voltage  
Measurement range up to   10 ... 600 V
Resolution   1 V
Accuracy   ±(1 % of Rd. +5 digits)
Overload   2000 V AC max. 1 minute
   
Insulation resistance  
Test voltage DC   250 V
Measurement range up to   2 M Ω ... 20 GΩ
Resolution   0,01 M Ω
Accuracy   ±(5 % o Rd +10 digits)
   
Insulation resistance  
Test voltage DC   500 V, 1000 V
Measurement range up to   1 M Ω ... 20 GΩ
Resolution   0,01 M Ω
Accuracy   ±(5 % o Rd +10 digits)
   
Insulation resistance  
Test voltage DC   2000 V
Measurement range up to   3 M Ω ... 200 GΩ
Resolution   0,01 M Ω
Accuracy   ±(5 % o Rd +10 digits)
   
Insulation resistance  
Test voltage DC   2500 V
Measurement range up to   5 M Ω ... 200 GΩ
Resolution   0,01 M Ω
Accuracy   ±(5 % o Rd +10 digits)
   
General technical data  
Measuring functions   HOLD, PI, DAR
Display type   LCD
Display size   3,7 Inch
Storage medium   Internal memory
Storage capacity   100 Data records
Standard(s)   EN 61010-1
Automatic power-off   25 min
Safety standard   CAT III 1000V, CAT IV 600 V
Menu language   English
Protection class (device)   IP20
Weight   651 g
Operating conditions   0 ... 35 °C , 0 ... 75 % RH
Storage conditions   0 ... 35 °C , 0 ... 75 % RH
   
(Rechargeable) battery   8 x 1,5 V AA battery , Alkali-manganese
Capacity   2500 mAh
Dimensions ( L x W x H )   140 x 180 x 70 mm