SCHNEIDER ACTI9 K60H 3P 40A B CURVE MCB — 10KA

The Schneider Electric Acti9 K60H 3P 40A Miniature Circuit Breaker (MCB) features a B-curve thermal-magnetic trip and 10kA breaking capacity for dependable overload and short-circuit protection. Built for DIN rail installations, it offers 6 × 9 mm module width, robust tunnel terminals, and compliance with EN/IEC 60898-1.

Specifications

  • Range: Acti9

  • Product Name: Acti9 K60

  • Device Short Name: K60H

  • Product Type: Miniature circuit-breaker (MCB)

  • Device Application: Distribution

  • Poles Description: 3P (3 protected poles)

  • Rated Current (In): 40 A

  • Trip Unit Technology: Thermal-magnetic

  • Curve Code: B (magnetic 3…5 × In)

  • Breaking Capacity (Icn): 10 kA at 230 V AC 50/60 Hz (EN/IEC 60898-1)

  • Rated Service Breaking Capacity (Ics): 10 kA (75%) at 400 V AC 50/60 Hz

  • Utilisation Category: Category A (IEC 60947-2)

  • Suitability for Isolation: Yes (EN/IEC 60898-1)

  • Limitation Class: 3 (EN/IEC 60898-1)

  • Network Type / Frequency: AC, 50/60 Hz

  • Rated Insulation Voltage (Ui): 440 V AC

  • Rated Impulse Withstand (Uimp): 4 kV

  • Mounting Mode / Support: Fixed, DIN rail

  • Comb Busbar Compatibility: Downside biconnect

  • 9 mm Pitches (Modules): 6

  • Connections – Terminals: Tunnel type (downstream) 0.5…35 mm² rigid

  • Wire Stripping Length: 14 mm (top/bottom)

  • Tightening Torque: 3.5 N·m (top/bottom)

  • Local Signalling / CPI: Without / No

  • Control Type: Toggle

  • Dimensions (W × H × D): 54 mm × 81 mm × 70 mm

  • Net Weight: 0.36 kg

  • Colour: White (RAL9003)

  • IP Degree of Protection: IP20 (IEC 60529)

  • Mechanical Durability: 20,000 cycles

  • Electrical Durability: 10,000 cycles

  • Pollution Degree / Overvoltage Category: 2 / II

  • Tropicalisation: 2 (IEC 60068-1)

  • Operating Altitude: 0…2000 m

  • Operating Temperature: −25…70 °C

  • Storage Temperature: −25…85 °C

  • Standards / Certification: EN/IEC 60898-1; VDE

Safety Note
Install and commission by a licensed electrician. Verify coordination with upstream protective devices and observe ambient temperature and torque limits during installation.

Ask about this product