testo 420 - volume flow hood
Product no. 0563 4200Technical data
Temperature - NTC
| Measuring range |
-20 to +60 °C
|
|---|---|
| Accuracy |
±0.8 °C (-20 to +0 °C)
±0.5 °C (0 to +60 °C)
|
| Resolution |
0.1 °C
|
| Reaction time |
45 s (t₉₀)
|
Humidity - Capacitive
| Measuring range |
0 to 100 %RH
|
|---|---|
| Accuracy |
±1.0 %rF/year Drift
±0.03 %RH/K (at 0 to 60 °C )
±1.0 %rF Hysterese
±1.8 %RH +3 % of mv (at 25 °C, 5 % to 80 %RH)
|
| Resolution |
0.1 %RH
|
Differential Pressure - Piezoresistive
| Measuring range |
-120 to +120 Pa
|
|---|---|
| Accuracy |
±2 % of mv + 0.5 Pa at +22 °C, 1013 hPa
|
| Resolution |
0.001 Pa
|
| Reaction time |
1 s (t₉₀)
|
Absolute Pressure
| Measuring range |
700 to 1100 hPa
|
|---|---|
| Accuracy |
±3 hPa
|
| Resolution |
0.1 hPa
|
| Reaction time |
1 s
|
Volume flow
| Measuring range |
50 to 4000 m³/h
|
|---|---|
| Accuracy |
1013 hPa (85 to 3500 m³/h)
±3 % of mv + 12 m³/h at +22 °C
|
| Reaction time |
1 s (t₉₀)
|
| Resolution |
1 m³/h
|
General technical data
| Weight |
2900 g
|
|---|---|
| Dimensions |
610 x 610 mm (Standard hood)
|
| Operating temperature |
-5 to +50 °C
|
| System requirements |
requires iOS 12.0 or newer; requires Android 6.0 or newer; requires mobile end device with Bluetooth 4.0
|
| EU-/EG-guidelines |
EU-guideline 2014/30/EU
|
| Battery life |
40 h
|
| Battery type |
Alkali manganese, mignon, type AA
|
| Display function |
Dot matrix
|
| Display ligthing |
with illumination
|
| Display size |
3.5"
|
| Data transfer |
Bluetooth®
|
| Interface |
Micro-USB; Bluetooth® 4.0 wireless technology
|
| Radio range |
10 m
|
| Memory |
2 GB (internal)
|
| Storage temperature |
-20 to +60 °C
|