Products

PRO0021-6200 Datalogging Power Clamp

Category: Clamp meters
  • Analysis for Single Phase and Balanced 3 phase system
  • True RMS Value (V and I)
  • Active Power (K,KW,MW,GW)
  • Apparent (VA,KVA,MVA) and Reactive Power (VAR,KVAR,MVAR)
  • Power Factor (PF), Phase Angle( Φ )
  • Energy (WH,KWH,KVARH,PFH)
  • Programmable PT(1 to 3000)Ratios
  • Display of Overlapped Voltage and Current Waveform
  • Maximum Demand (MD in W,KW,MW) with programmable Period
  • Harmonic Analysis (V and I) to 50th Order
  • Display of 25 Harmonics in one screen
  • Optical Isolated RS-232C Interface
  • Smart Datalogging to save Battery 

 

  • Analysis for Single Phase and Balanced 3 phase system
  • True RMS Value (V and I)
  • Active Power (K,KW,MW,GW)
  • Apparent (VA,KVA,MVA) and Reactive Power (VAR,KVAR,MVAR)
  • Power Factor (PF), Phase Angle( Φ )
  • Energy (WH,KWH,KVARH,PFH)
  • Programmable PT(1 to 3000)Ratios
  • Display of Overlapped Voltage and Current Waveform
  • Maximum Demand (MD in W,KW,MW) with programmable Period
  • Harmonic Analysis (V and I) to 50th Order
  • Display of 25 Harmonics in one screen
  • Optical Isolated RS-232C Interface
  • Smart Datalogging to save Battery
  • Datalogging of 32,64,128 or 256 points/cycles
  • Analysis of Total Harmonic Distortion (%THD-F)
  • Graphic Phasor Diagram
  • Capture 128 Transient Events (Time+Cycles+Faults) with Programmable Threshold(%),also can be reviewed in LCD
  • 50000 Records with Programmable Interval (1 to 6000 seconds)
  • Real-time Output of Waveform, Power Parameters and Harmonics at Command
  • Large Dot Matrix LCD Display with Backlight
  • Power for Long-term Monitoring
  • Built -in Calendar Clock for Data Logging

General Specification:

 
     

Conductor Size

55mm(approx.), 64*24mm(bus bar)

Battery Type

Two 1.5 V SUM-3

Display

128*64 Dot Matrix

Power Consumption

10 mA (approx.)

Auto - Power - Off

30 minutes after power-on

Update time

2 times/sec. (display)

No. of Samples per Period

512 (voltage or current)256 (power)

Operating Temperature

-10 to 50

Operating Humidity

<85% RH

Storage temperature

-20 to 60

Storage Humidity

<75% RH

Dimension

210 mm (L) * 62 mm (W) * 35.6 mm (H)8.3"(L) * 2.5 "(W) * 1.4"(H)

Weight

Test leads *1 pair, Carrying bag*1, Users manual*1, Batteries 1.5V*2

Accessories

640g

AC Current (50 or 60 Hz, Auto Range, True RMS)

Range

Resolution

Accuracy of Reading

4.0 V - 1500.0 A

0.01 A

± 0.5 % ± 5 dgts

AC Voltage (50 or 60 Hz, Auto Range, True RMS)

Range

Resolution

Accuracy of Reading

4.0 - 600.0 V

0.1 V

± 0.5 % ± 5 dgts

Harmonics of AC Voltage in Percentage and Magniude(1 to 50th order)

Range

Resolution

Accuracy (in%)


  1. (in Magnitude)

1 – 20 th

0.1 %

± 2 %

± 2 % ± 0.5 V

20 – 50 th

0.1 %

4 % of reading ± 2 %

4 % of reading ± 0.5 V

Harmonics of AC Current in Percentage and Magnitude (1 to 50th order)

Range

Resolution

Accuracy (in %)

Accuracy
(in Magnitude)

1 – 20 th

0.1 %

± 2 %

± 2 % of reading ± 0.4 A

20 – 50 th

0.1 %

4 % of reading ± 2 %

± 4 % of reading ± 0.4A

Power Factor (PF)

Range

Resolution

Accuracy (>20 V and >20 A)

0.000 - 1.000

0.001

± 0.04

Phase Angle ( Φ )

Range

Resolution

Accuracy (>20 V and >20 A)

-180 ° to 180 ° (0 ° to 360 ° )

0.1 °

±1 °

Total Harmonic Distortion(%THD-F1 to 50th order)

Range

Resolution

Accuracy (>20 V and >20 A)

0.0 - 20%

0.1%

± 2 %

20 - 100%

0.1%

± 6 % of reading ± 1 %

100 - 999.9%

0.1%

± 10 % of reading ± 1 %

Crest Factor (C.F.)

Range

Resolution

Accuracy of Readings

1.00 - 99.99

0.01

± 5 % ± 30 digits

AC Watt (50 or 60 Hz, PF 0.5 to 1, CT=1)

Range

Resolution

Accuracy of Readings
(>20V and >20A)

10.0 - 999.9 W

0.1 W

± 1% ± 20 dgts

1.00 - 9.999 KW

0.001 KW

± 1% ± 20 dgts

10.00 - 99.99KW

0.01 KW

± 1% ± 20 dgts

100.0 - 999.9 KW

0.1 KW

± 1% ± 20 dgts

1000 - 9999 KW

1 KW

± 1% ± 20 dgts

 
Ask about this product